D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
• Pri mode :
TEMP 1
= mode set by programme :
– TEMP 1…5
= control with one of
Desired Primary temp
– OFF
= control Off
• Td 20.0 c = value of desired temp. for current mode.
• Var +
0.0
c = manual variation of desired temp. (use + or – keys),
with B1 max ± 10 °C, with B3 max ± 5 °C.
13.5 Temperature set point adjuster
If setpoint adjuster Rt° is connected and configured, it is possible to adjust from a distance
value of current desired temp. within the limits set :
The value of the adjustment made is shown on the display.
13.
6 Variation programmes by remote control
If the remote control R is connected and configured in
it is possible to modify from a distance the current operating programme :
1 –
OFF
= plant excluded
2 –
TEMP 4
= continuous operation at desired temperature 4
3 –
TEMP 3
= continuous operation at desired temperature 3
4 –
TEMP 2
= continuous operation at desired temperature 2
5 –
TEMP 1
= continuous operation at desired temperature 1
6 –
AUTOMATIC
= operation with programme chosen on controller.
13.7 Primary zone priority function
Primary zone priority: NO
= function excluded
YES
= function enabled
When RTR 684 is connected in C-Ring with other controllers and the Priority function has been
enabled :
– Primary control sends via C-Ring the differential value between its own desired temperature
and the actual one;
– the C-Ring controllers with the
Anticondensing
function enabled reduce their own desired flow
temperature by 4 °C for each °C difference so as to give precedence to the primary control of
DTR 684.
Note When Priority function is used and plant boiler requests the presence of anticondensing detector it
is indispensable to connect it to the first RTR 684 in the C-Ring.
13.8 Control pump plant M1
The plant pump can be controlled in two ways :
Pri Pump : MAN
= pump always in operation
AUT
= pump controlled by event times of current programme
Delay Off : - - m
= delay time in switching Off
Setpoint ad j us t
Td : + 0 . 0c
19.4
19.3
Pr i mode:TEMP 1
Td20.0cVar+ 0.0c
Setpoint adjust
min l imi t : 0.0c
22.18
Se t po i nt ad j us t
max l imi t : + 0 . 0c
22.19
Pr imary zone
priori ty : NO
22.21
P r i pump : AUT
De l ay Of f : 0m
22.22
Con f i g de t ec t o r s
––––––7
24.1