15
D 215 - RTR 684 C2 Eng. 14.06.00
We reserve the right to make changes without notice
COSTER
19. NORMAL USE
Ref Display Description Notes Sect.
19.1 Pri:------------
12 . 18 MONDAY
Name primary zone
Current time and day
Set in 22.23
Set in 19.7
19.2 Pri:------------
24HOUR 1 PR IMARY
Name primary zone
Choice programme :
24 HOUR 1…4 PRI ;
7DAY PRI ; TEMP 1…5 ; OFF.
Instead of programme may appear :
REMOTE TEMP 1…4 ; REMOTE OFF.
13.4
19.3
Pr i mode:TEMP 3
Td21.0cVar+ 0.0c
Current operating mode :
Td
: Desired temp. for mode
Var
: Variation of desired temp.
Pri mode :
TEMP 1…5 ; OFF.
Var : use + or – keys (with B1 max ± 10 °C ; with B3
max ± 5 °C
13.4
19.7 12 . 18 MONDAY
10. 02 .96 GMT
Setting : time, day of week & date
Current time period : GMT or BST According dates BST period set in 21.31
19.12
RTR 684 Eng . C2
Ver s . xx
Identifying data of controller.
20. TEMPERATURES
Ref. Display Description Notes Sect.
Desi red Primary
temp 1 20.0c
20.1
Value of desired temp. 1 for primary zone 13.4
Des i r ed Aux
temp 20.0c
20.6
Value of desired temp. for auxiliary zone 14.2
Desi red Primary
temp 2 20.5c
20.2
Value of desired temp. 2 for primary zone 13.4
Desi red Primary
temp 3 21.0c
20.3
Value of desired temp. 3 for primary zone 13.4
Desi red Primary
temp 4 19.5c
20.4 Value of desired temp. 4 for primary zone 13.4
Desi red Primary
temp 5 19.0c
20.5
Value of desired temp. 5 for primary zone 13.4
19.4 Se tpo i nt adj us t
Td : + 0 . 0c
Variation of temperature set on set-point adjuster 13.5Appears only if set-point adjuster Rt° has been
configured in 24.1
.
19.5 Aux:------------
24HOUR 1 AUX
Name auxiliary zone
Choice programme:
24HOUR 1…3 AUX ;
7DAY AUX ; ON ; OFF.
Set in 23.8 14.2
19.6 Aux mode : ON
Td20.0cVar+ 0.0c
Current operating mode :
Td
: Desired temp. for mode
Var
: Variation of desired temp.
Aux mode :
ON ; OFF.
Var : use + or – keys (max ± 10 °C).
14.2
Des Pr i T : 21 . 0c
Ac t Pr i T : 20 . 0c
19.8
Temperature desired for primary control.
Temperature measured by detector B1 or B3.
16.4
Des Aux T : 20 . 0c
Ac t Aux T : 20 . 0c
19.10
Desired flow temp. for auxiliary control.
Temperature measured by detector B5.
16.4
Appears only if detector B5 configured in 24.1
.
Des f l ow T : 50 . 0c
Ac t f l ow T: 50 . 0c
19.9
Desired flow temp. for primary control.
Temperature measured by detector B2.
16.4
Appears only if detector B2 configured in 24.1
.
Des an t i cT: 50 . 0c
Ac t an t i cT : 50 . 0c
19.11 Desired anticondensing temperature.
Temperature measured by detector B4.
16.4
Appears only if detector B4 configured in 24.1
.