14. AUXILIARY CONTROL
If detector B5
is not connected and not configured
, output M2
can be used as a time switch with programme chosen in
If detector B5
is connected but not configured
it functions only as a temperature monitor
If detector B5
is connected and configured
in
the auxiliary control, according to programme chosen in
compares the temperature measured with desired temperature set in
and produces the On-Off control action of output M2 according to temperature difference and
parameters set :
if
•
Diff : – – . – c
= On-Off stage differential
if
•
Prop band : – – . – c
= proportional band in ± °C
•
Integ time : – – m
= integral time in minutes
•
Half cycle time – – – sec
= start and stop time when actual temp. is equal to desired temp.
14.1 Control output M2
The start and stop controls of output M2 depend not only on the control parameters set but also on :
•
Minimum start time : – – sec
= minimum start time
•
Minimum stop time : – – sec
= minimum stop time
•
Delay Off
: – –
min
=
delay time in switching off : when output controls pump of a primary zone
and boiler is controlled, via C- Ring, by maximum temperature requested by zone controllers,
this permits dissipating residual heat in combustion chamber.
14.2 Operating mode
The
Desired Aux temp
is used in establishing the three programmes of timed events 24 HOUR 1 …3
AUX which , in turn, are used to establish the 7-day programme 7DAY AUX.
It is possible to programme the operation of the auxiliary control according to the requirements of
the zones :
–
7 DAY AUX
= in operation 7-day programme with timed events
– 24 HOUR 1 …3 AU
X = in operation one of three 24-hour progs. with timed events
– ON
= continuous operation at
Desired Aux temp
– OFF
= always Off
The current
operational mode
depends on programme set
.
• Pri mode :
ON
= mode set by programme
– ON
= control by
Desired Aux temp
– OFF
= control Off
• Td 20.0 c = temperature desired by current mode
• Var +
0.0
c = manual adjustment of desired temperature (use + or – keys)
max ± 10 °C.
Con f i g de t ec t or s
5
24.1
Des i r ed Aux
temp: 50.0c
20.6
Con t r o l :ON-OFF
PROPORT I ONAL
23.1
Prop band : 10 . 0c
Integ time: 10m
23.2
Di f f :10.0c
23.2
Con t r o l :ON-OFF
D I FFERENT I AL
23.1
Ha l f cyc l e t ime
120sec
23.3
Minimum star t
time : 60s
23.4
Minimum stop
time : 60s
23.5
Auxiliary pump
De l ay Of f : 0 mi n
23.7
Aux:------------
24 HOUR 1 AUX
19.5
19.5
Aux:------------
24HOUR 1 AUX
19.6
Aux mode :ON
Td20 . 0cVar+ 0 . 0c
Des i r ed Aux
temp 20.0c
20.6
Aux:------------
24HOUR 1 AUX
19.5
Des Aux T : –– . –c
Ac t Aux T : 50 . 0c
19.10