13.2 Control with primary detector (B1 or B3) & flow detector (B2)
RTR 684 compares temperature measured by detector B1 or B3 with desired temperature of current
programme T°d and calculates
desired flow temperature
T°fd in relation to difference measured
and parameters set. :
•
Prop band : – – . – c
= proportional band Pb in ± °C of primary
control
•
Integ time : – – m
= integral time in minutes of primary control.
•
Min : – – c Max : – – C
= minimum and maximum limits of flow temp.:
establish range of proportional band of primary control (22.
9 - 22.13).
The controller compares temperature measured by flow detector B2 with value calculated T°fd and
adopts control action Y1 or E1 in relation to difference measured and parameters set.
if
•
Prop band : – – . – c
= proportional band Pbf in ± °C of flow control
if
•
Diff : – – . – c
= On-Off differential of stage ∆t° of flow control
13.3 Control output Y1
The control output of the primary control Y1 (1-2 ; 3-4) can be :
• Control :
MODULATING
= control valve by three-wire modulating actuator
ON-OFF DIFF
= On-Off control in two stages
If
MODULATING ,
enter :
– complete run time (open/closed) of valve actuator ; indispensable for correct control operation.
– dead band Db of modulating action : NARROW ; MEDIUM ; WIDE.
If ON-OFF DIFF, enter if necessary for electric device controlled :
– minimum start time of On-Off control
– minimum stop time of On-Off control
13.
4 Operating mode
You can set five temperatures
Desired Primary temp
1 ... 5
to be used in creating the four programmes of timed events 24HOUR 1 ... 4
PRI
.
which in turn are used for creating the 7-day programme 7DAY PRI.
It is possible to programme the operation of the primary control according to the requirements of
the zones :
–
7DAY PRI
= operation with timed events using 7-day prog.
– 24HOUR 1 …4 PRI
= operation with timed events using one of four 24-hour progs.
– TEMP 1…5
= continuous operation using one of five desired temperatures.
– OFF
= always Off
when in place of programme appears :
–
REMOTE TEMP 1…4
= remote control R is in “Temperature 1 ... 4” position.
–
REMOTE OFF
= remote control R is in “Off” position.
The current
operational mode
depends on the programme set.
Con t r o l :
MODULAT I NG
22.1
Ac t ua tor run t ime
630sec
22.2 - 22.8
Minimum star t
time : 60s
22.6 - 22.16
Minimum stop
time : 60s
22.7 - 22.17
Prop band : 10 . 0c
Integ time: 10m
22.9 - 22.13
Con t r o l f l ow
Min: 1c Max:99c
22.11 - 22.15
Flow temp
Prop band : 10 . 0c
22.10
Dead band
NARROW
22.4 - 22.12
Flow temp
Di f f :10.0c
22.14
Con t r o l :
MODULAT I NG
22.1
Con t r o l :
ON-OFF DI FF
22.1
19.2
Pri:------------
24HOUR 1 PR IMARY
Des i r ed Pr imar y
temp 1 20.0c
20.1 - 20.5
t°
+
T°
f
T°
d
Pb
d
–
T°f
max.
T°f
min.
T°
f
d
∆t°
E1
off
–
+
∆t°
off
on
on
E1.
2
E1.
1
t°f
T°f
d
t°
f
Pb
f
Y1
100%
0%
–
+
Db
50%
T°
f
d